Solar Battery Backup Time Calculator
Model battery bank capacity, inverter efficiency, depth of discharge, and load wattage to estimate real backup runtime — with an animated energy‑flow diagram.
Battery & Load Inputs
Nominal voltage — 12 V, 24 V, 48 V for lead‑acid / LiFePO₄ banks.
Amp‑hour rating at the 20‑hour rate (C/20). Energy = V × Ah.
Current available charge before discharge begins.
Maximum safe discharge. Lead‑acid ≈ 50 %, LiFePO₄ ≈ 80–90 %.
Typical pure sine wave inverters: 85–95 %. Include wiring losses.
Continuous AC load. Add 20–30 % headroom for surge if needed.
Solar charging reduces net discharge and extends runtime during daylight.
Energy Flow
Live diagramRuntime Results
Estimated Backup Time
≈ 6 h 24 min
Theoretical
2400
Wh
Usable Energy
1536
Wh
Current Charge
1920
Wh
Remaining
0
Wh after load
Formula: Runtime = (V × Ah × SoC × DoD × ηinv) ÷ LoadW. Solar input offsets load during daylight hours.
Real‑world note: Actual runtime is typically 10–20 % lower due to Peukert effect, temperature, inverter idle draw, and battery age. Use this estimate as an upper bound.
1 Ah vs Wh — Why both matter
Amp‑hours (Ah) measure charge capacity — how much current a battery can deliver over time. Watt‑hours (Wh) measure energy, which is what actually runs your appliances.
A 12 V, 200 Ah battery stores 12 × 200 = 2,400 Wh of theoretical energy. A 24 V, 100 Ah battery stores the same 2,400 Wh — same energy, different voltage/current trade‑off. Always convert to Wh before comparing batteries or calculating runtime.
Wh = V × Ah
Example: 48 V × 100 Ah = 4,800 Wh
2 Depth of Discharge (DoD) & battery chemistry
DoD is the percentage of total capacity you can safely use before recharging. Discharging a lead‑acid battery below 50 % regularly shortens its life dramatically. LiFePO₄ (lithium iron phosphate) tolerates 80–90 % DoD with minimal degradation.
| Chemistry | Typical DoD | Cycle life |
|---|---|---|
| Flooded lead‑acid | 50 % | 300–500 |
| AGM / Gel | 50–60 % | 500–800 |
| LiFePO₄ | 80–90 % | 3,000–7,000 |
3 Inverter efficiency — the hidden loss
Inverters convert DC battery power to AC household power. This conversion isn't 100 % efficient — 5–15 % is lost as heat. A 92 % efficient inverter means 8 % of your battery energy never reaches the load.
Why this matters: a 2,400 Wh battery with 92 % inverter efficiency delivers only 2,208 Wh of AC energy. Always include inverter efficiency in runtime calculations — it's one of the biggest real‑world derating factors.
Typical efficiency ranges
- • Modified sine wave: 75–85 %
- • Pure sine wave (budget): 85–90 %
- • Pure sine wave (premium): 90–96 %
4 Load wattage & surge
Load wattage is the continuous power your appliances draw. But many loads — motors, compressors, pumps — have a surge (inrush) current 2–3× their running wattage for a few seconds.
For runtime calculations, use continuous wattage. For inverter sizing, use surge wattage. A refrigerator might run at 150 W but surge to 600 W on compressor start.
Common continuous loads
5 Solar charging — extending runtime
During daylight, solar panels offset your load and recharge the battery. A 600 W array in 4.5 peak sun hours produces roughly 2,700 Wh/day — but after charge controller losses (~95 % efficiency) and wiring losses, expect 2,300–2,500 Wh usable. If your load draws 400 W continuously, solar covers about 5–6 hours of that load per day, significantly extending battery runtime.
Step 1
Solar production
Array W × peak sun hours × 0.75 (derate)
Step 2
Net battery drain
Load − solar production (if positive)
Step 3
Extended runtime
Usable Wh ÷ net drain
6 Worked example — 12 V, 200 Ah LiFePO₄
Given
- Battery voltage12 V
- Capacity200 Ah
- State of charge80 %
- Depth of discharge80 %
- Inverter efficiency92 %
- Load400 W
Calculation
- 1. Theoretical energy = 12 × 200 = 2,400 Wh
- 2. Usable energy = 2,400 × 0.80 × 0.80 = 1,536 Wh
- 3. After inverter = 1,536 × 0.92 = 1,413 Wh
- 4. Runtime = 1,413 ÷ 400 = 3.53 h ≈ 3 h 32 min
With 600 W solar (4.5 sun hours) covering ~5 h of load, runtime extends to roughly 6–7 h net.